Lumen, lux and watt: the difference and how to calculate with them
Watt tells you what a luminaire consumes, lumen what it emits and lux what actually arrives on the working plane. Here is how you convert between them and choose the right output for each application.
Three units, three questions
They sit side by side on every datasheet, yet they answer three different questions. Watt (W) states what the luminaire draws from the mains: the power consumed, driver included. Lumen (lm) states how much light the luminaire emits in total: the luminous flux. Lux (lx) states how much of that light lands on a given surface: the illuminance, defined as lumen per square metre.
For you as an installer, lux is what counts: the client wants 200 lux on the warehouse floor or 500 lux on the desk, not a number of watts on the ceiling. Watt matters for the energy bill and the circuit design; lumen is the intermediate step from luminaire to illuminance.
Lumen per watt: the efficacy
Divide luminous flux by power and you have the efficacy in lumen per watt (lm/W). A 100 W high bay with 15,000 lm achieves 150 lm/W; the 100 W version with 18,000 lm from the ATRIA range reaches 180 lm/W. That is 20 per cent more light for the same consumption, or the same light with 20 per cent fewer luminaires.
For comparison: halogen manages at most 20 to 25 lm/W, fluorescent tubes and metal halide sit around 80 to 100 lm/W. On top of that, a conventional fitting loses part of the lamp output in its reflector and ballast, whereas an LED module emits directionally. Hence the rule of thumb that a 400 W metal halide high bay is replaced by an LED high bay of 150 to 200 W.
Always compare luminaire lumens (light leaving the fitting) with luminaire lumens and not with lamp lumens of the LED chip, and check whether the stated wattage includes the driver.
From lumen to lux: area and height
The basic formula: lux = installed lumens × utilisation factor × maintenance factor ÷ area in m². The utilisation factor is the share of light that actually reaches the working plane and depends on mounting height, beam angle and the reflectance of walls and ceiling; for LED high bays in a hall usually 0.6 to 0.8. The maintenance factor (often 0.8) allows for dirt and ageing, so the installation still meets the standard years later.
Worked example: a warehouse of 40 by 25 metres (1,000 m²) needs 200 lux on the floor. Required on the floor: 200 × 1,000 = 200,000 lm. Divided by 0.7 (utilisation) and 0.8 (maintenance) that is 357,000 lm installed. With an 18,000 lm UFO high bay that means 20 luminaires, at 100 W each 2 kW of connected load. The same 20 units at 15,000 lm would give roughly 170 lux: just short.
Mounting height follows the inverse square law: hang the luminaire twice as high and you get a quarter of the lux directly beneath it. So in a taller hall choose not just more lumens but also a narrower beam: a UFO with 120° up to about 7 metres, 90° above that, and over narrow racking aisles a linear high bay with a 30 by 90° beam, so the light falls into the aisle rather than onto the top pallet.
Rules of thumb per application
The European standard for workplace lighting gives a minimum maintained average illuminance on the working plane for each task. The values you will need most often:
- Warehouse and storage: 150 lux in aisles with forklift traffic, 300 lux in picking and packing zones
- Production hall: 300 lux for rough work, 500 lux for assembly and inspection, 750 lux or more for fine work
- Office: 500 lux on the desk, with UGR<21 to limit glare on screens
- Sports hall: 300 lux for training and recreation, 500 lux for competition
- Covered car park: 75 lux on lanes and bays, more at the entrance and exit
- Outdoor car park: 5 to 20 lux, depending on traffic intensity
- Residential street and cycle path: 3 to 7.5 lux average, depending on the lighting class
- Tennis and padel court: 300 lux at club level, 500 lux for competition
A 25 W street luminaire with 1,500 lm from the VIA range on a 4 metre TURRIS column is intended for exactly such a residential street or cycle path; the VIA luminaires are made for a 60 mm spigot and fit these steel columns. For a car park you move to 50 to 100 W on 6 metres; the column spacing follows from the lighting calculation.
Common mistakes
- Comparing wattage instead of luminous flux: 100 W means nothing until you know the lumens
- Measuring lux at the wrong height: in an office the working plane is at desk height, roughly 0.75 to 0.85 m above the floor, in a warehouse it is the floor itself
- Forgetting the maintenance factor: an installation that just reaches 200 lux when new drops below the standard after a few years
- Looking only at average lux: the standard also sets uniformity requirements, usually 0.4 to 0.6 between lowest and average value
- Ignoring glare: in offices and sports halls UGR is as decisive as the lux level
Colour temperature (2700 K to 5000 K) changes nothing about the lux, but a great deal about perception: 4000 K for halls and offices, 2700 to 3000 K for residential streets and parks. The IP rating plays no part in the lux calculation but does in the maintenance factor: a sealed luminaire in IP65 or IP66 stays clean inside.
Calculate yourself or have it calculated
For a rectangular hall with one luminaire type this formula gets you well within tolerance. As soon as racking, varying heights, daylight or outdoor areas with columns come into play, a lighting calculation pays off: it calculates point by point, checks uniformity and glare and delivers a report for the client. Lichtplein prepares such a calculation for 350 euro excl. VAT based on your floor plan and the required lux levels, for businesses only.
Frequently asked questions
How many lumens per square metre do I need?
Divide the required lux by roughly 0.55 (utilisation times maintenance factor). For 200 lux in a hall that is about 360 lm per m² installed, for 500 lux in an office about 900 lm per m².
Is more watt always more light?
No. A 100 W luminaire at 180 lm/W emits more light than a 120 W luminaire at 140 lm/W. Always compare lumens and lm/W, and use watts only for the energy calculation.
What is the difference between lumen and candela?
Lumen is the total luminous flux, candela the luminous intensity in one direction. Candela becomes relevant with narrow optics, such as stadium floodlights with a 30° beam on a tall mast, where the same lumens are concentrated into a small angle.
How high can I mount a 100 W high bay?
As a rule of thumb: 100 W up to about 7 metres, 150 W up to 10 metres and 200 to 240 W above that, with a narrower beam as the hall gets taller. Above 10 metres a lighting calculation is advisable.
Why does my installation deliver less lux than calculated?
Usually because of an optimistic utilisation factor, dark walls or racking absorbing light, or because lamp lumens were used instead of luminaire lumens. Always measure on the working plane and compare with the calculated value after the maintenance factor.
Want to be sure your design meets the standard? Request a lighting calculation or browse the ATRIA high bays and VIA street luminaires in the range.
Read also
KnowledgeLED lighting before year end: KIA, EIA and planning for Dutch businesses
Many companies replace their lighting in the last months of the year. What the Dutch small-scale investment allowance (KIA) and energy investment allowance (EIA) can mean, what to watch out for and how to have the luminaires on site in time.
28 October 2026
KnowledgeSite lighting for the dark months: checklist for business sites and car parks
Once the clocks go back it is dark by half past four, and the first and last hour of the working day happen in the dark. How to check your outdoor lighting now, fill the gaps and have the luminaires on site before the shortest days.
25 October 2026
NewsNew: steel and aluminium lighting columns to the Dutch standard
Lichtplein now supplies conical steel lighting columns of 4 and 6 metres at a sharp price on request, plus aluminium columns of 3, 4 and 6 metres. With full dimensions on the product page, matching our street and post-top luminaires, delivered by truck.
8 October 2026
Worked examplesWorked example: a 4,000 m² warehouse from fluorescent to LED high bay
A fictional hall of 80 by 50 metres, 10 metres high, 200 lux required. Step by step we work out how many 150 W UFO high bays are needed, what that saves per year in kWh compared with fluorescent, and what sensors add on top.
8 October 2026