Office lighting: lux, UGR and continuous light lines to the standard
500 lux on the desk, UGR 19 and a uniformity of 0.60: that is what the standard asks for office work. Here is how to turn those requirements into continuous light lines, the choice between pendant and surface mounting and the right wattage setting.
What the standard requires on the working plane
The requirements for office lighting are set out in EN 12464-1, the European standard for the lighting of indoor workplaces. For writing, typing, reading and screen work it asks for 500 lux on the working plane: the desktop, taken in the calculation as a horizontal plane 0.75 m above the floor. This is a maintained value, meaning the level that must still be reached after ageing and soiling.
Lower values apply around the task area: at least 300 lux in the immediate surroundings and 100 lux in the background. Other office functions have their own requirements:
- Meeting room: 500 lux, UGR 19
- Reception: 300 lux, UGR 22
- Archive: 200 lux, UGR 25
- Corridors: 100 lux, UGR 28
The standard also asks for a uniformity Uo of at least 0.60 on the working plane (lowest value divided by the average), a colour rendering index Ra of at least 80 and light on walls and ceiling, in the order of 50 to 75 lux on the walls and 30 to 50 lux on the ceiling, depending on the edition of the standard. An office that only lights the desks feels gloomy, even when the 500 lux is there.
UGR 19: controlling glare through the layout
UGR (Unified Glare Rating) expresses how much direct glare an installation produces; for desk work the limit is UGR 19. The UGR on a datasheet is a tabular value for a reference room. What you achieve in your project depends on the room dimensions, the mounting height, the reflectances and the viewing direction of the staff.
Three factors make the difference in practice:
- Viewing direction: lines running parallel to the line of sight give a lower UGR than lines running across the desk.
- Luminance above 65 degrees: for screen work the standard limits the brightness of the luminaire at shallow viewing angles so that it does not reflect in the screen. An opal or microprismatic diffuser keeps that brightness low.
- Background: a light ceiling and light walls reduce the contrast and with it the UGR.
The LINEA linear luminaires have UGR<21 as their tabular value. In an actual office with a light ceiling and lines parallel to the viewing direction the calculated value is often lower, but whether you reach 19 must be shown by the lighting calculation.
Linking light lines: from single luminaire to continuous run
A light line consists of modules that you link mechanically and electrically into one continuous run: no visible joint and one supply point per line instead of per luminaire. That saves installation time and cable. The LINEA modules link seamlessly and are available in white and black.
When setting out the lines, keep in mind:
- Line spacing: at a mounting height of 2.7 to 3 m, 2 to 3 m between the lines is usually right for 500 lux and Uo 0.60.
- Position: the line beside or between the desks, not directly above the screen, parallel to the viewing direction.
- Facade: the first line 1 to 1.5 m from the window so that the daylight zone is not lit twice.
- Ordering: count per room the modules per line, the number of lines, the colour and the uplight modules.
Pendant or surface mounted, and the indirect share
Surface mounting is the choice for ceiling heights up to about 2.7 m and for suspended ceilings with no free space above. The luminaire sits against the ceiling and all the light goes downwards. Pendant mounting becomes interesting from about 2.8 m: you suspend the line 0.3 to 0.6 m below the ceiling, closer to the working plane.
The big advantage of pendant mounting is the indirect share. An uplight module sends part of the light to the ceiling, which reflects it diffusely. The ceiling itself becomes a light source: less contrast, lower UGR, softer shadows on the desk, and the wall and ceiling values from the standard are met more easily. For LINEA a separate indirect uplight module is available that you combine per module on the line.
Indirect light only works with a light ceiling: reckon with a reflectance of 0.7 for white. A dark or open ceiling with exposed services swallows most of it. In that case choose surface mounting or a pendant without uplight.
Selectable wattage: 24, 32 or 40 W per module
The LINEA linear luminaire has a selectable wattage: 24, 32 or 40 W, set with a switch on the driver. At 120 lm/W that is roughly 2,900, 3,800 or 4,800 lumens per module. You order one article for the whole office and set the wattage per room during installation:
- Open-plan office: 40 W for 500 lux.
- Corridor or kitchenette: 24 W, where 100 to 200 lux is enough.
- Higher ceiling: one setting higher for the same lux on the working plane.
- After measuring: too much light? One setting lower and you save energy straight away.
Set the wattage before installation, with the supply isolated, and record the setting per room in the handover file.
Worked example: open-plan office of 48 m²
An open-plan office of 8 by 6 m, ceiling height 2.8 m, white ceiling, light walls, eight workstations in two rows. Required on the working plane: 48 m² × 500 lux = 24,000 lumens. Not all the light reaches the working plane and the installation ages; reckon with a room utilisation of about 0.65 and a maintenance factor of 0.8. That gives roughly 24,000 / (0.65 × 0.8) ≈ 46,000 lumens of installed luminous flux.
Two lines of five modules at 40 W give 48,000 lumens at 400 W, or 8.3 W/m². Three lines of four modules at 32 W give 46,000 lumens at 384 W and better uniformity, because the line spacing drops from 3 to 2 m. The second option needs more modules but meets Uo 0.60 more easily and leaves room to go one setting higher later. Which option fits your ceiling and what the UGR per workstation will be is worked out by a lighting calculation for 350 euros excl. VAT.
Frequently asked questions
Is 500 lux mandatory?
EN 12464-1 is a standard, not a law. Occupational health and safety legislation does require adequate lighting, and in practice clients, insurers and inspectors test against this standard. Do not design below it without a good reason.
Can I use a UGR<21 luminaire where UGR 19 is required?
Yes, provided the calculation for your room shows UGR 19 or lower. The tabular value is a reference; room size, ceiling reflectance and the orientation of the lines determine the result.
How many modules do I need per square metre?
As a rule of thumb at 2.8 m ceiling height: one 40 W module per 4 to 5 m² for 500 lux. The calculation is decisive.
Pendant or surface mounted with a suspended ceiling?
Both are possible: surface mounted on the ceiling grid or suspended from the structural ceiling through the tiles, as long as enough height remains below the line.
Can I change the wattage later?
Yes. Isolate the supply and move the wattage switch on the driver. Record the new setting in the file.
View the LINEA linear luminaires or have your office calculated via a lighting calculation: you receive lux, UGR and uniformity per room plus a parts list that goes straight into your quotation request. Lichtplein supplies businesses only.
Read also
KnowledgeLED lighting before year end: KIA, EIA and planning for Dutch businesses
Many companies replace their lighting in the last months of the year. What the Dutch small-scale investment allowance (KIA) and energy investment allowance (EIA) can mean, what to watch out for and how to have the luminaires on site in time.
28 October 2026
KnowledgeSite lighting for the dark months: checklist for business sites and car parks
Once the clocks go back it is dark by half past four, and the first and last hour of the working day happen in the dark. How to check your outdoor lighting now, fill the gaps and have the luminaires on site before the shortest days.
25 October 2026
KnowledgeUFO or linear high bay: which one for your warehouse or hall
A high bay comes as a round UFO, as a linear luminaire above the racking aisle and as a flat panel with UGR<21. Which one you choose depends on mounting height, racking and the work done in the hall. This article gives the selection rules and a worked example for the number of luminaires.
8 October 2026
Knowledge3000K, 4000K or 5000K: choosing colour temperature by application
Kelvin decides whether light looks warm, neutral or cool, and with it whether a street feels comfortable and a warehouse works well. We set out the right colour temperature for each application.
7 October 2026